Accessories | 1 - Preliminary considerations
Circuit-breaker dismantling
operations
To dismantle the accessories, the following parts must be removed from the circuit-breaker:
• Escutcheon plate (A) and protection (F) by removing the screws (B and C).
• For circuit-breakers in four-pole versions, the lateral protection (D) by removing the screws (C and E).
A
D
C
E
B
F
Figure 69 - Removing the escutcheon plate and protections
After reassembling the accessories, the parts previously disassembled must be reassembled as indicated:
• Escutcheon plate (A) and protection (F) by screwing the fixing screws (B and C). Lock with tightening
torque 0.8 Nm - 7 lb in (B) and 1.5 Nm - 13 lb in (C).
• For circuit-breakers in four-pole versions, the lateral protection (D) by removing the screws (C and E).
Tighten with tightening torque 1.5 Nm - 13 lb in.
A
D
B
C
E
F
Figure 70 - Assembly of escutcheon plate and protections
8mm
0,5 2,5mm
2
2
1
0,5 1,5mm
2
20 AWG16AWG
20 AWG14AWG
Max O 3,3mm
Max O,301 "
Max O 3,3mm
Max O,301 "
0.31"
8mm
0.31"
Figure 71 cables mounting with stripping and sections