Interface and menus | 4 - Menu23 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
Installation menu
If Ekip Touch detects that Rating Plug or Measurement module have not been installed properly, it signals an
alarm (page 50) and completes Settings menu with the specific installation section:
Menu Submenus 1 Submenus 2 Commands
Circuit Breaker Installation
Rating Plug Install
Ekip Measuring Install
Correct installation is confirmed by a message on the display and disappearance of the alarm signal and
installation menu.
NOTE: availability of submenus depends on the module, which appears to have not been
installed
Test Menu
Menu Submenus Description, parameters and Commands
Autotest - Autotest command
Trip Test - TRIP command
Test CB - Close CB, Open CB
Ekip Signalling 4K
(1)
- Module autotest command
Ekip Signalling 2K
(1)
Ekip Signalling 2K-1
(1)
Module autotest commandEkip Signalling 2K-2
(1)
Ekip Signalling 2K-3
(1)
ZoneSelectivity
(2)
S Protection
Input, Force Output, Release Output
G Protection
Rc Test
(5)
- Test instructions
(1)
available if one or more Ekip Signalling modules are connected and detected by Ekip Touch
(2)
available if Ekip Touch is on with auxiliary supply
(3)
available with S and/or S2 protection enabled and curve t=k
(4)
available with G and/or Gext protection enabled and curve t=k
(5)
available with Rating Plug and Rc sensor present
About Menu
Menu Submenus Information provided
Protection Unit -
Information about Ekip Touch: Mainboard serial
number, Trip unit serial number, type, version,
standard, SW version, date and time, language
Circuit Breaker -
CB information: TAG name, CB name, rated current,
number of poles, CB status and position, total
operations, CB serial number
IEC61557-12
(1)
-
Status of 1% measurements (from Class 1 Power
& Energy Metering package), serial number of
assembly and current sensors connected
Feature Collection - List of tripped protections in Trip unit
Modules Modul x
(2)
Module information: serial number, SW version,
status of inputs/outputs/contacts (if present)
Power Controller
(3)
Load Input Status Status of loads (open/closed)
Load Active Load configuration (activated/not activated)
Load shedding
(3)
Load Input Status Status of loads (open/closed)
Load Active Load configuration (activated/not activated)
(1)
available if Class 1 Power & Energy Metering SW package is provided for by Trip unit module or if it has been
previously activated
(2)
available if one or more modules are connected and detected by unit
(3)
available if function has been installed and enabled in Trip unit