ABB | SACE Emax 2
Ekip Touch protection release | 17 - Test
143 | © 2013 ABB | 1SDH001000R0002 - L7804
Continued from the previous page
RC test
Submenus for the test of the Rc sensor involve the command Self-test. that allows the
command to be sent to the RC sensor to check on the correct operation.
NOTE: the test is available only with sensor correctly connected, release in Rc
configuration, auxiliary power supply present.
Protection test
To perform the protection command test, follow the following procedure:
Phase Operation
1
Make sure that the circuit-breaker is closed and that there are no currents
circulating
2 Connect a test front unit between Ekip T&P or Ekip Bluetooth
3 Start the communication with Ekip Connect
4
Open the Information page and select the Test command, which opens the
protection test page
5 Set up the test as required and verify that the release functions properly