9
3. Technical characteristics
3.1. Electrical data
C Module
Switch-
disconnector
Switch-
disconnector
F Module
Switch-
disconnector
with fuses
Earthing
switch
on load side
V Module
Vacuum
circuit-breaker
Earthing
switch
Rated voltage kV
Withstand voltage
at industrial frequency kV
Impulse withstand voltage kV
Rated current A
Breaking capacities:
- under load A
- rated ring A
- no-load cables A
- no-load transformer A
- earth fault A
- cables with earth fault A
- on short-circuit kA
Making capacity kA
Short-time withstand current 1s kA
Short-time withstand current 3s kA
SafeRing
12/17.5/24
28
(1)
/38/50
95/95/125
630/630/630
630/630/630
630/630/630
135/135/135
200/150/150
115/87/87
52.5/40/40
21/16/16
12/17.5/24
28
(1)
/38/50
95/95/125
52.5/40/40
21/16/16
12/17.5/24
28
(1)
/38/50
95/95/125
(2)
20/20/20
(3)
(3)
12/17.5/24
28
(1)
/38/50
95/95/125
12.5/12.5/12.5
05/05/05
12/17.5/24
28
(1)
/38/50
95/95/125
200/200/200
21/16/16
52.5/40/40
21/16/16
12/17.5/24
28
(1)
/38/50
95/95/125
52.5/40/40
21/16/16
C Module
Switch-
disconnector
Switch-
disconnector
F Module
Switch-
disconnector
with fuses
Earthing
switch
on load side
V Module
Vacuum
circuit-breaker
Earthing
switch
Rated voltage kV
Withstand voltage
at industrial frequency kV
Impulse withstand voltage kV
Rated current A
Breaking capacities:
- under load A
- rated ring A
- no-load cables A
- no-load transformer A
- earth fault A
- cables with earth fault A
- on short-circuit kA
Making capacity kA
Short-time withstand current 1s kA
Short-time withstand current 3s kA
SafePlus
12
(1)
/17.5/24
281/38/50
95/95/125
630/630/630
630/630/630
630/630/630
135/135/135
200/150/150
115/87/87
62.5/52.5/52.5
25/-/-
21/21/21
12
(1)
/17.5/24
281/38/50
95/95/125
62.5/52.5/52.5
25/-/-
21/21/21
12
(1)
/17.5/24
281/38/50
95/95/125
(2)
20/20/20
(3)
(3)
12
(1)
/17.5/24
281/38/50
95/95/125
12.5/12.5/12.5
05/05/05
12
(1)
/17.5/24
281/38/50
95/95/125
630/630/630
21/16/16
52.5/40/40
21/16/16
12
(1)
/17.5/24
281/38/50
95/95/125
52.5/40/40
21/16/16
1) 38 kV on request
2) According to the rated current of the fuse
3) Limited by the fuses
The SafeRing RMU/SafePlus CSG system undergoes tests according to the IEC 60056, IEC 60129, IEC 60265, IEC 60298, IEC 60420 and IEC
60694 Standards.