D184B122U02 S4 37
Submenu/
Parameter
Submenu/
Parameter
Submenu/
Parameter
Selections
Value Range
Comments
HART TAG Text entry
A unique instrument identifier using the
HART TAG Number. Max 8-character TAG-
Number (PCKASCII String). Only capital let-
ters are recognized, no special characters
can be used.
No entries possible for Standard
instruments (no HART-Hardware).
„HART TAG“
HART Descriptor Text entry
Description max. 16-character (PCKASCII
String). Only capital letters are recognized,
no special characters can be used.
No entries possible for Standard
instruments (no HART-Hardware).
„HART Descriptor“
HART Date
Day
Month
Year
A date can be entered and read here.
Not available for Standard instruments
(no HART-Hardware).
03.11.2003
PA Address
Numeric
entry 0–125
2. Communication PROFIBUS PA
Only available if the Variant PROFIBUS PA
was ordered.
Display of the Slave Address. Factory set-
ting 126 (valid Addresses 0-125).
The PA-Address can be entered using the
following functions:
Hardware switch (see Section 8.5.2), Bus or
the menu PA-Address. The hardware
switch setting has the highest priority. An
Address set using the hardware switch can-
not be changed, either over the Bus or using
the menu. If the switch address setting is
not active, DIP-Switch 8=OFF, then the
Address can be set over the Bus or the
menu, but only if cyclic communication is
not active.
126
DipSwitch view only
Display indicating which DIP-Switches are
set ( - = OFF, X = ON). If the DIP-Switch 8 =
ON: the Address setting can be binary
coded using switches 1-7. Switches 9 and
A have no function.
Example: Set Address 50 using the swit-
ches. 50dec=32hex = 110010 binary
DIP-switch 2, 5, 6 and 8 to ON = PA-Ad-
dress 50. An Address-switch setting
change is only recognized after the instru-
ment is rebooted, not if changed during nor-
mal operation. Factory setting for the switch
is : OFF
123456789A
_ _ _ _ _ _ _
IdentNo Selctor
Setting the Ident-Number-Selectors.
The settings cannot be changed when cycli-
cal operation is not active, only during status
STOP.
Profile 0x078C: AI + 2* TOT (AI-Block + 2
Totalizer)
FSM4000 0x078C
AI + 2* TOT
IdentNo Selctor
Profile 0x9700 (AI-Block)
ENTER
Profile 0x9700
AI
IdentNo Selctor
Profile 0x9740 (AI-Block + Totalizer)
profile 0x9740
AI + TOT

Table of Contents