SM500F
Field mountable paperless recorder 7 Configuration
IM/SM500F Rev. Z 91
Note. Displayed only if 'Archive file format' is set to 'Text format'.
Set the frequency with which new channel data files are created.
Note. Set automatically to 'Off' if 'Wrap' (see next page) is set to 'On'.
New File Interval Filename
Hourly <hour> <day, month, year>* <filename tag>
Daily <day, month, year>* <filename tag>
Monthly <month, year>* <filename tag>
None <filename tag>
*Formatted according to the date format set in Common Configuration –
see Section 7.6.3, page 76.
When set to 'On', archive wrap deletes automatically the oldest archived
data file from external archive media when the media approaches its
maximum capacity.
When set to 'Off', archiving stops automatically when external archive
media is full. No files are deleted.
Oldest Un-archived Data
Archive Triggers
<1 Day Old (Binary)
or <1 Hour Old (Text)
>1 Day Old (Binary)
or >1 Hour Old (Text)
'Online' request from the
Logging menu.
Any un-archived data is stored
automatically to the removable
archive media.
All the un-archived data within the
selected time frame is archived.
Older un-archived data remains in
the internal memory buffer until
overwritten by newer data but is
not available for archiving to
removable media.
Automatic update Any un-archived data is saved to
removable archive media at regular
intervals (approximately every 30
seconds).
Not Applicable
Table 7.2 Archive Triggers