PR8 - 2 WBPEEUI240751C0
Procedure
4. Set the analog input field power select jumpers J17 and
J18 located on the AIN-220 base (Table PR8-2). These jumpers
affect channels configured as IFP or LFP powered 4 to 20 milli-
ampere inputs. Refer to Figure PR8-1 for jumper locations.
Figure PR8-2 shows the field power connections made with
jumpers J17 and J18.
5. Set the input channel jumpers located on the AIN-220 base
(Table PR8-3). Refer to Figure PR8-1 for jumper locations.
Table PR8-1. F ield Power Sele ct Jumpers (Module)
Field Power J1 J2 Description
IFP
1
Field power f rom mounting
column bus
LFP Field power from LFP
terminals on base
NOTE:
1. Use this setting if all channels are RFP powered.
123 123
123 123
C1
Table PR8-2. A nalog Input Field Power Select Jumpers (Base)
Field Power J17 J18 Description
Fused AI
IFP/LFP
1
Routes IFP/LFP field power
through the fuse in the I/O
module.
Unfused AI
LFP
2,3
Routes LFP power directly to
the base terminals.
NOTES:
1. This option can be selected to provide fused IFP or LFP power to the analog input channels;
however, removing the I/O module from the base in a nonredundant application will result in a loss
of power to all input current loops.
2. Use this setting if current loop power must be maintained when the I/O module is removed from
the base in nonre dundant app lications.
3. Use this setting if analog inputs are RFP powered. Use this option if stations are connected.
123 123
123 123
Table PR8-3. Input C hannel Jumpers
Input
Field
Power
n
1
-J1 n
1
-J2
4 to 20 mA IFP/LFP
RFP
Differential high level
voltage
RFP
321 321
321 321
321 321