TruONE® ATS, INSTALLATION AND OPERATING INSTRUCTION
1
TOUCH
Parameters *Default
System parameters
Start Automatic Configuration
Power distribution systems (see Fig. 2.2)
Source 1 1 Phase, 2 Wire
2 Phases, 3 Wire (Split Neutral)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
Source 2 1 Phase, 2 Wire
2 Phases, 3 Wire (Split Neutral)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
Rated Voltage 200 V (3ph), 208 V (3ph), 220 V (3ph), 230 V (3ph), 240 V (3ph),
277 V (3ph), 347 V (3ph), 380 V (3ph), 400 V (3ph)*, 415 V (3ph),
440 V (3ph), 460 V (3ph), 480 V (3ph), 200 V (1ph), 220 V (1ph),
230 V (1ph), 240 V (1ph), 254 V (1ph), 265 V (1ph), 277 V (1ph),
318 V (1ph), 333 V (1ph), 347 V (1ph), 380 V (1ph), 400 V (1ph),
415 V (1ph), 440 V (1ph), 460 V (1ph), 480 V (1ph)
Rated Frequency 50 Hz*
60 Hz
Neutral Position Pole 4*
Pole 1
Phase Sequence ABC*
ACB
Not Enabled