VortexMaster FSV430, FSV450 SwirlMaster FSS430, FSS450 | CI/FSV/FSS/430/450-EN  Rev. G  5 
 
2  Use in potentially explosive 
atmospheres 
2.1  Obligations of the owner 
2.1.1  Ex-marking 
If the device manufacturer has not specified the type of 
protection on the name plate, the operator must specify the 
type of protection used on the name plate, by permanent 
means, during installation of the device. 
 
2.1.2  ATEX, IECEx, NEPSI 
The installation, commissioning, maintenance and repair of 
devices in potentially explosive atmospheres must only be 
carried out by appropriately trained personnel. Works may be 
carried out only by persons, whose training has included 
instructions on different types of protection and installation 
techniques, concerned rules and regulations as well as general 
principles of zoning. The person must possess the appropriate 
competences for the type of work to be conducted. 
When operating with combustible dusts, comply with 
EN 60079-31. 
The safety instructions for electrical apparatus in potentially 
explosive areas must be in accordance with Directive 
2014/34/EC (ATEX) and IEC60079-14 (Installation of electrical 
equipment in potentially explosive areas). 
Comply with the applicable regulations for the protection of 
employees to ensure safe operation. 
 
2.1.3  FM / CSA 
The installation, commissioning, maintenance and repair of 
devices in areas with explosion hazard must only be carried 
out by appropriately trained personnel. 
The operator must strictly observe the applicable national 
regulations with regard to installation, function tests, repairs, 
and maintenance of electrical devices. (e.g. NEC, CEC). 
 
 
 
The following tables provide an overview of the approvals 
available for explosion protection. 
 
Type of protection "intrinsic safety" (Ex ia / IS) 
 
Approval Order code 
ATEX (Europe)  A4 
IECEx N2 
NEPSI (China)  S6 
FM (USA and Canada)  F4 
 
Type of protection "flameproof enclosure" (Ex d ia / XP-IS) 
 
Approval Order code 
ATEX (Europe)  A9 
IECEx N3 
NEPSI (China)  S1 
FM (USA and Canada)  F1 
 
Type of protection "non-sparking" (Ex n / NA) 
 
Approval Order code 
ATEX (Europe)  B1 
IECEx N1 
NEPSI (China)  S2 
FM (USA and Canada)  F3 
 
Combined approvals 
In the case of combined approvals, the user decides on the 
type of protection during installation. 
 
Type of protection  Order code 
ATEX Ex n + Ex ia  B8 = B1 + A4 
ATEX Ex n + Ex ia + Ex d  B9 = B1 + A4 + A9 
IEC Ex Ex n + Ex ia  N8 = N1 + N2 
IEC Ex Ex n + Ex ia + Ex d   N9 = N1 + N2 + N3 
NEPSI Ex n + Ex ia  S8 = S2 + S6 
NEPSI Ex n + Ex ia + Ex d   S9 = S2 + S1 + S6 
cFMus NA + IS  F8 = F3 + F4 
cFMus NA + IS + XP-IS  F9 = F3 + F4 + F1