6.6 System Initialization
The instrument can be reset to the default configuration by mean of the System initialization function.
To enter the system initialization mode , the user must enter the instrument control mode and use the F key
to select the modality:
S Y S I N I T
and press the E key.
The instrument will ask for password and, if correct, the following message will be displayed:
* I N I T *
Press the E key to request to start the sequence and the instrument prepares to receive the confirmation
command:
O K I N I T ?
flashing
Press the E key to confirm the selection made and the instrument initializes the parameters and restarts
automatically.
Press the C key to cancel the initialization request and return to the instrument control menu.
6.6.1 Switch controlled initialization
Initialization by switch can only be performed at power-on time.
The procedure is the following:
? DIP switch SW1-4 must be ON prior to power on
? The display shows the message:
O K I N I
flashing
? if the switch is setted to OFF in less than 5 seconds the initialization is carried out and the message on
display changes to
I N I T
flashing
and stays in this condition as long as a key is pressed, thus proceeding with startup sequence.
? if the switch is left unchanged the instrument proceeds with normal startup sequences