A pop-up screen lets you scroll through the various timer types available.
Pulse - A water meter activated timer
Limit - Feed with bleed with a maximum run time or limit
for one bleed cycle.
Recycle - A continuous recycle timer with ON and OFF
settings.
Percent Post Bleed - For feed after bleed for a settable
percentage of the bleed time with a maximum run time.
28-Day - A biocide or event timer.
4.2 Timer Set Up
Each timer type selected will have its own unique Set Up

of timer selected. The page displayed before entering
the Set Up menu of a timer provides an overall review

4.3 Pulse Timer
ACCUMULATE - The number of gallons or liters from
water meter to count before activating timer.
RUN TIME - The amount of time for the timer to run
METER INPUT - Select water meter 1 or 2 for the

only if the meters have the same contact value.
BLEED INTR - Allows the pulse timer to be interrupted
during conductivity bleed. While interrupted, you can
        
(1-9) to store for playback.
4.4 Recycle Timer
ON CYCLE 
timer is to be on.
OFF CYCLE - The amount of time that the cycle will be
󰀨
ON/OFF TIMER - This is the displayed count down of
time for the cycle the timer is in.
4.5 Post Bleed Timer
>SYSTEM 1 TIMER 1 SET UP<
>SET TIMER TYPE (PULSE)<
-> PULSE
USE UP/DOWN KEYS TO CHANGE
PRESS ENTER TO ACCEPT
SET UP TIMER TYPE
>SYSTEM 1 TIMER 1 SET UP<
TIMER TYPE: PULSE
GALLONS: 10
RUN TIME (MM:SS): 01:00
INPUT: WATER METER 1
SET UP TIMER TYPE
>SYSTEM 1 TIMER 1 CHANGE<
ACCUMULATE
RUN TIME
METER INPUT BLEED INTR
>SYSTEM 1 TIMER 1 CHANGE<
ON CYCLE (HH:MM)
OFF CYCLE (HH:MM)
OFF TIMER (HH:MM:SS): 0:10:40
>SYSTEM 1 TIMER 1 CHANGE<
% OF BLEED
LIMIT TIME
SOURCE

Other manuals for Advantage Controls MegatronXS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantage Controls MegatronXS and is the answer not in the manual?

Advantage Controls MegatronXS Specifications

General IconGeneral
BrandAdvantage Controls
ModelMegatronXS
CategoryController
LanguageEnglish

Related product manuals