Maximum Series Portable Chiller : Air & Water-Cooled : MG Series Instrument
Page: 83
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
If calibration of this probe is required, repeat the setup and calibration procedure
with the “from process” probe. A from process probe may not be included with
your chiller.
8. Stop the unit following the shutdown procedure described in the manual and
place all process probes back in the unit to return to normal operation.
From Process
Calibration
Potentiometer
From Process
Calibration
Potentiometer
To Process
Calibration
Potentiometer
To Process
Calibration
Potentiometer