4-130 ADAM 4000 Series User's Manual
Command Set
4021
%AANNTTCCFF
Example command: %310A310610(cr)
response: !24(cr)
The analog input module at addresses 31h is configured to a
new address 0Ah, output range 4 to 20 mA, baud rate 9600,
engineering units data format, a slew rate of 1.0 mA/sec and no
checksum checking.
The response indicates that the command has been received.