Command Set
4-18 ADAM 4000 Series User's Manual
Range
code(Hex)
Input Range Max. Signal Min Signal
Displayed
Resolution
07 +/-4~20 mA +20.000 -20.000 1uA
08 +/-10 V +10.000 -10.000 1mV
09 +/-5 V +5.0000 -5.0000 100.00uV
0a +/-1 V +1.0000 -1.0000 100.00uV
0b +/-500 mV +500.00 -500.00 10uV
0c +/-150 mV +150.00 -150.00 10uV
0d +/-20 mA +20.000 -20.000 1uA
Input range and external calibrating input source for each
input type