EasyManuals Logo
Home>Advantech>Other>Adam-4018

Advantech Adam-4018 User Manual

Advantech Adam-4018
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #177 background imageLoading...
Page #177 background image
Chapter 4 Command Set 4-
93
4018M
Chapter 4
@AASO
Name Set Memory Operation Mode
Description Sets the operation mode of the analog input data logger at
address AA to Start or Stop.
Syntax @AASO(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input data logger.
S identifies the Set Memory Operation Mode command.
O represents the operation mode: 1 enables the recording of
data. 0 disables the recording of data.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command is valid.
?AA(cr) if an invalid parameter was entered. There is no
response if the module detects a syntax error or communication
error or if the specified address does not exist.
! is a delimiter character indicating a valid command was
received.
? is a delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of an analog input data logger.
(cr) is the terminating character, carriage return (0Dh).
Example command: @03S1(cr)
response: !03(cr)
The command enables the analog input data logger at address
03 to record data.
The response indicates that the command was received.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam-4018 and is the answer not in the manual?

Advantech Adam-4018 Specifications

General IconGeneral
BrandAdvantech
ModelAdam-4018
CategoryOther
LanguageEnglish

Related product manuals