2-8 ADAM 4000 Series User's Manual
Installation Guideline
To change the configuration setting of the analog input module, the
following command is issued:
%01070F0600(cr)
% = change configuration
01 = target module at address 00 to:
07 = change address to 07 hexadecimal
0F = set input range to Type K thermocouple
06 = set baud rate to 9600
00 = set integration time to 50 ms (60 Hz)
disable checksum
set data format to engineering units
(See Chapter 4, Command Set for a full description of the syntax of the
configuration command for an analog input module)
When the module received the configuration command it will respond with
its new address:
!07(cr)
Wait 7 seconds to let the new configuration settings take effect before
issuing a new command to the module.
NOTICE: All reconfiguration except changing of baud rate and checksum
values can be done dynamically, i.e. the modules need not to be reset.
When changing the baud rate or checksum, these changes should be made
for all connected devices. After reconfiguration, all modules should be
powered down and powered up to force a reboot and let the changes take
effect. See the next page for a strategy for changing baud rate and or
checksum for an entire network.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam-4018 and is the answer not in the manual?

Advantech Adam-4018 Specifications

General IconGeneral
BrandAdvantech
ModelAdam-4018
CategoryOther
LanguageEnglish

Related product manuals