Name Synchronized Sampling
Description Orders all (analog or digital) input modules to sample their input
values and store them in a special register.
Syntax #**
# is a delimiter character.
** is the actual Synchronized Sampling command.
The terminating character, in the form of a carriage
return (0Dh), is not required.
Response The digital I/O modules will not respond to the Synchronized
Sampling command. In order to retrieve the data, you must
execute a Read Synchronized Data command for every module
separately.