EasyManua.ls Logo

Advantech Adam-4018

Advantech Adam-4018
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-206 ADAM 4000 Series User's Manual
4080
Command Set
@AADAN
Name Disable Alarm
Description Disable Alarm for the specified counter
Syntax @AADAN (cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
DAN represents the Disable Alarm Mode for counter command.
N = 0 Represents counter 0
N = 1 Represents counter 1
(cr) is the terminating character, carriage return (0Dh).
Response !AA(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! is a delimiter character indicating a command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12DA0(cr)
response: !12(cr)
The counter module at address 12h is instructed to disable the
alarm functions for counter 0. The module confirms its alarm
functions have been disabled.

Table of Contents

Related product manuals