Unitdoesnotstart
Lackofelectricalvoltage
Checkelectricalvoltageispresent
Checktheupstreamsafetydevicesprovidingpower
totheunit
GeneralisolatorisOFF
RemotecontactisOFF(ifpresent)
ControlpanelisOFF
MainisolatorisOFF
CompressorcircuitbreakerisOFF
PlaceinON
Powersupplyvoltagetoolow Checkpowersupply
Compressorcontactorcoilfaulty
Electronicboardfaulty
Startingcapacitorfaulty
Compressorfaulty
Replacethecomponent
Lowcapacityoutput
Lackofrefrigerantcharge
Condensercoildirty
Waterfilterclogged
Unitlocation
Operatingoutsideoflimits
Checkchargeandforleaks
Cleancondensercoil
Cleanwaterfilter
Checkperformance
Checkagainstoperatinglimitcharts
Compressornoisy
Liquidrefrigerantreturntocompressor
Inadequatefixingdown
Checkandcorrect
Phasereversal Reverseonephase(400V/3N/50Hzonly)
Noiseandvibrations
Contactbetweenmetalcomponents Checkandcorrect
Weakbasesupport Improvebasesupport
Loosefixings Tightenfixings
Compressorstopsonsafeties
Dischargepressuretoohigh
Suctionpressuretoolow
Powersupplyvoltagetoolow
Electricalconnectionsloose
Operatingoutsideoflimits
Checkagainstoperatinglimitschart
Pressostatfaulty Replacethecomponent
Thermalcut-outoperates
Checkvoltageandsettings
Checkinsulationofwindings
Compressordischargepressurehigh
Externalairtemperaturehigh
Systemwaterinlettemperaturehigh
Checkagainstoperatinglimitschart
Insufficientairflow
Insufficientwaterflow
Check:
1. fanoperation
2. condensercoilclean
3. pumpoperation(andspeed)
4. waterfilterclean
Faultyfancontrol Checkandreplaceiffaulty
Airinwatercircuit Ventcircuit
Refrigerantchargetoohigh Checkchargeandadjust
Dischargepressurelow
Externalairtemperaturelow
Systemwaterinlettemperaturelow
Checkagainstoperatinglimitschart
Moistureinrefrigerantcircuit Removechargeandreplace
Airinwatercircuit Ventcircuit
Refrigerantchargetoolow Checkchargeandadjust
Suctionpressurehigh
Externalairtemperaturehigh
Systemwaterinlettemperaturehigh
Thermostaticexpansionvalvetooopenorfaulty
Checkagainstoperatinglimitschart
Adjustorreplaceiffaulty
Suctionpressurelow
Systemwaterinlettemperaturelow
Externalairtemperaturelow
Thermostaticexpansionvalvefaultyorobstructed
Checkagainstoperatinglimitschart
Adjustorreplaceiffaulty
Insufficientwaterflow
Insufficientairflow
Check:
1. fanoperation
2. condensercoilclean
3. pumpoperation(andspeed)
4. waterfilterclean

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC Variable Multi Flow ANL 580 and is the answer not in the manual?

AERMEC Variable Multi Flow ANL 580 Specifications

General IconGeneral
BrandAERMEC
ModelVariable Multi Flow ANL 580
CategoryChiller
LanguageEnglish

Related product manuals