24
18.03. 5719210_03
ANL / 290-650
EN
 
  
Unitdoesnotstart
Lackofelectricalvoltage
Checkelectricalvoltageispresent
Checktheupstreamsafetydevicesprovidingpower
totheunit
GeneralisolatorisOFF
RemotecontactisOFF(ifpresent)
ControlpanelisOFF
MainisolatorisOFF
CompressorcircuitbreakerisOFF
PlaceinON
Powersupplyvoltagetoolow Checkpowersupply
Compressorcontactorcoilfaulty
Electronicboardfaulty
Startingcapacitorfaulty
Compressorfaulty
Replacethecomponent
Lowcapacityoutput
Lackofrefrigerantcharge
Condensercoildirty
Waterfilterclogged
Unitlocation
Operatingoutsideoflimits
Checkchargeandforleaks
Cleancondensercoil
Cleanwaterfilter
Checkperformance
Checkagainstoperatinglimitcharts
Compressornoisy
Liquidrefrigerantreturntocompressor
Inadequatefixingdown
Checkandcorrect
Phasereversal Reverseonephase(400V/3N/50Hzonly)
Noiseandvibrations
Contactbetweenmetalcomponents Checkandcorrect
Weakbasesupport Improvebasesupport
Loosefixings Tightenfixings
Compressorstopsonsafeties
Dischargepressuretoohigh
Suctionpressuretoolow
Powersupplyvoltagetoolow
Electricalconnectionsloose
Operatingoutsideoflimits
Checkagainstoperatinglimitschart
Pressostatfaulty Replacethecomponent
Thermalcut-outoperates
Checkvoltageandsettings
Checkinsulationofwindings
Compressordischargepressurehigh
Externalairtemperaturehigh
Systemwaterinlettemperaturehigh
Checkagainstoperatinglimitschart
Insufficientairflow
Insufficientwaterflow
Check:
1. fanoperation
2. condensercoilclean
3. pumpoperation(andspeed)
4. waterfilterclean
Faultyfancontrol Checkandreplaceiffaulty
Airinwatercircuit Ventcircuit
Refrigerantchargetoohigh Checkchargeandadjust
Dischargepressurelow
Externalairtemperaturelow
Systemwaterinlettemperaturelow
Checkagainstoperatinglimitschart
Moistureinrefrigerantcircuit Removechargeandreplace
Airinwatercircuit Ventcircuit
Refrigerantchargetoolow Checkchargeandadjust
Suctionpressurehigh
Externalairtemperaturehigh
Systemwaterinlettemperaturehigh
Thermostaticexpansionvalvetooopenorfaulty
Checkagainstoperatinglimitschart
Adjustorreplaceiffaulty
Suctionpressurelow
Systemwaterinlettemperaturelow
Externalairtemperaturelow
Thermostaticexpansionvalvefaultyorobstructed
Checkagainstoperatinglimitschart
Adjustorreplaceiffaulty
Insufficientwaterflow
Insufficientairflow
Check:
1. fanoperation
2. condensercoilclean
3. pumpoperation(andspeed)
4. waterfilterclean