1. Plateheatexchanger
2. Waterfilter
3. Flowswitch
4. Airvent
5. Watertemperaturesensors(IN/OUT)
8. Safetyvalve
11. Gauge
14. Drainvalve

4. Airvent
6. Anti-vibrationjoints
7. Isolatingvalve
9. Expansiontank
10.
Systembuffertank(installationrecommendedifthetotalsystemwatercontentislessthanthat
indicatedinthetablebelow)
12. Pump
13. Electricanti-freezeheater
14. Drainvalve




5
5
1
3
8
9
6
6
4
14
10
4
14
13
7
7
7
7
11
2
WARNING
Theselectionandinstallation
ofcomponentsexternaltothe
unitaretheresponsibilityofthe
installerandmustbecarriedout
inaccordancewithgoodworking
practicesandapplicablestandards
ofthecountryofdestination.
WARNING
Thehydraulicpipingtotheunit
mustbeadequatelysizedforthe
requiredflowrate.Thewaterflow
ratethroughtheheatexchanger
mustalwaysbeconstant.
WARNING
Carefullycleanthesystempriorto
connectiontotheunit.Thisclean-
ingeliminatesweldingslag,dirt,
rustoranyotherimpuritiesfrom
thepiping.Theseimpuritiesmay
otherwisebedepositedwithin
theunitandcauseamalfunction
Theconnectingpipingmustbe
adequatelysupportedsoasnotto
imposeanyweightontotheunit.
WARNING

Duringthewinterperiodthewater
intheheatexchangermayfreeze
whenthesystemisoff,causing
irreversibledamagetotheheat
exchanger.
Therearethreesolutionstoavoid
theriskoffreezing
 
theunit.
 with
apercentageofglycolse-
lectedinaccordancewiththe
minimumanticipatedexternal
temperature.
 .
Insuchcasestheelectricheat-
ersmustalwayshavepower
availableforthewholeperiod
ofpossiblefreezing(unitin
stand-by)
 290 300 340 400 580 620 650
Numberofcompressors 2 2 2 2 2 2 2
Minimumrecommendedwatercontent l/kW 4 4 4 4 4 4 4
System: Chiller with plate heat exchanger
PH 7,5-9
Electric conductivity 100-500μS/cm
Total hardness 4,5-8,5 dH
Temperature < 65°C
Oxygen content < 0,1 ppm
Max. glycol amount 50%
Phosphates (PO4) < 2ppm
Manganese (Mn) < 0,05 ppm
Iron (Fe) < 0,3 ppm
Alkalinity (HCO3) 70 - 300 ppm
Chloride ions (Cl-) < 50 ppm
Sulphate ions (SO4) < 50 ppm
Sulphide ion (S) none
Ammonium ions (NH4) none
Silica (SiO2) < 30ppm


Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AERMEC Variable Multi Flow ANL 580 and is the answer not in the manual?

AERMEC Variable Multi Flow ANL 580 Specifications

General IconGeneral
BrandAERMEC
ModelVariable Multi Flow ANL 580
CategoryChiller
LanguageEnglish

Related product manuals