Rockwell Automation Publication 1606-RM003A-EN-P - March 2019 29
DC-UPS with Integrated battery - 24V, 10 A
As a result, the battery should be replaced after 2 years. The battery degradation
begins from the production date, which is shown on the battery, may shorten the
replacement interval.
Accessories
Battery
The battery should be replaced on a periodic basis. See Replacement Intervals for
more information.
Figure 29 - Battery
Figure 27 - Service Life versus Ambient Temperature, typ. Figure 28 - Cell Capacity Degradation versus Discharging
Cycles
Attribute Description
Battery type Nom 12V, 4…6 Ah VRLA lead acid maintenance-free battery
Design life Min 3…5 years Per EUROBAT guidelines
Dimensions Nom 70 x 106 x 90 mm
(2.75 x 4.17 x 3.54 in.)
W x H x D
(1)
(1) Maximum case height of 102 mm (4.01 in.).
Pole connection – 6.35 mm (0.25 in.) Blade type; fast-on
Approvals – UL, Vds For applications that require UL or V ds
Allowed discharge
current
Min 29 A Continuous