Rockwell Automation Publication 2100-IN012G-EN-P - August 2016 127
Auxiliary Contact Adapters Appendix B
Install External Auxiliary
Contact Adapter on G, H, J,
and K Frame Units
Follow these instructions to install an external auxiliary contact adapter in
Bulletin 2100 Series Z or later units with circuit breakers (Bulletin 140G and
140MG). The instructions are the same for single and dual units.
This auxiliary contact kit is to be used with the following auxiliary contacts:
Catalog numbers 800F-X10, 800F-X01, 800F-X20D, 800F-X11D, and
800F-X02D.
Required Tools
You need a screwdriver, a 1/4” wrench or socket, a 5/16” wrench or socket, and
a torque wrench.
Installation
Refer to Figure 51 and use the following steps to install external auxiliary
contact adapter.
1. Make sure that all of the power has been disconnected.
2. Verify the parts list.
3. Install auxiliary contacts.
4. Attach the external auxiliary contact assembly to the mounting plate by
using one #8-32 x 0.38 inch thread-rolling screw.
5. Tighten to these vaules:
20 lb•in (2.2 N•m) for #6-20 screws
32 lb•in (3.6 N•m) for #8-32 screws
6. Check continuity to ensure proper operation of auxiliary contacts.
TIP De-energize all of the power sources to the motor control center before
installing auxiliary contact adapter. Failure to de-energize all of the power
sources can result in severe injury or death.