Rockwell Automation Publication 2100-IN012G-EN-P - August 2016 129
Auxiliary Contact Adapters Appendix B
Install External Auxiliary
Contact Adapter on M and N
Frame Units
Follow these instructions for installing the auxiliary contact adapters on M and
N frame units.
Required Tools
You need a socket set with extension and a torque wrench to complete the
installation.
Install the Auxiliary Contact Adapter
Follow these steps and refer to Assembly of External Auxiliary Contact Parts to
install the auxiliary contact adapter.
1. Verify that all of the power has been disconnected and turn the operator
handle to the OFF/O position.
2. Verify the parts list, see Assembly of External Auxiliary Contact Parts
.
3. Attach the external auxiliary contact assembly to the mounting plate by
using two 1/4-20 thread-rolling screws and tighten to 55 lb•in
(6.2 N•m).
Refer to Assembly of External Auxiliary Contact Parts.
4. Attach the actuator to the circuit breaker bail by using two 1/4-20
thread-rolling screws.
5. Position the actuator so the screws are centered in the slots and tighten
to 55 lb•in (6.2 N•m).
6. Install the auxiliary contacts (catalog numbers 800F-X10, 800F-X01,
800F-X20D, 800F-X11D, and 800F-X02D).
7. Turn the operator handle to the ON/I position to verify that the
auxiliary contacts change state.
8. Check continuity to verify proper operation of auxiliary contacts.