58 Rockwell Automation Publication 2100-IN012G-EN-P - August 2016
Chapter 4 Installing and Removing Plug-in Units
b. Remove the hinge pins by sliding upward with a flathead screwdriver.
The control station can be hung on the front of the unit by using
square holes adjacent to the top unit latch.
For Units With Follow This Step
A control station First slide the hinge pin out of the hinge and through the tab on the control station
wiring.
ArcShield units with 100 ms
arc duration rating
Two hinges are required for each hinge leaf.
1. The upper hinge on each door must be removed from the structure to remove the
uppermost hinge pin.
2. Remove the hinge pin through the lower hinge, then through the hinge leaf and
upper hinge.
Only top hinge must
be removed to install
hinge pin.
Hinge for ArcShield Units with 100 ms Arc Duration Rating
Hinge
Hinge Leaf
Hinge Pin