14 Rockwell Automation Publication 2071-IN001F-EN-P - February 2017
Kinetix 3 Component Servo Drives
Ground Your Kinetix 3 Drive to the Subpanel
Bond the Kinetix 3 drive to the cabinet ground bus. To ground, attach a braided ground strap or
0.4 mm
2
(12 AWG) solid-copper wire, 100 mm (3.9 in.) long between the top mounting screw
and the bonded cabinet ground.
Item Description
1 Mounting screw
2 Braided ground strap
3 Bonded cabinet-ground bus
4 Ground grid or power distribution ground
5 2071-AP4 Kinetix 3 drive shown
3
4
2
1
5

Related product manuals