22 MicroLogix Analog Input/Output Module
Publication 1762-IN005A-US-P
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to
use in hazardous locations.
!
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for
Class I, Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must
be fully seated and the bus connector cover must be
snapped in place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
page 6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
All wiring must comply with N.E.C. article 501-4(b).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1762-IF2OF2 and is the answer not in the manual?

Allen-Bradley MicroLogix 1762-IF2OF2 Specifications

General IconGeneral
BrandAllen-Bradley
ModelMicroLogix 1762-IF2OF2
CategoryI/O Systems
LanguageEnglish

Related product manuals