Programming and Parameters 3-25
A110 [Anlg In 0-10V Lo] Related Parameter(s): d020, P034, P038, A051, A052
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than A111
[Anlg In 0-10V Hi] or by
setting A051
- A052 [Digital Inx Sel] to option 26 “Anlg Invert”
Values Default 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
0
P035 [Maximum Freq]
P034 [Minimum Freq]
A110 [Anlg In 0-10V Lo] A111 [Anlg In 0-10V Hi]
0
Speed Reference
A111 [Anlg In 0-10V Hi] Related Parameter(s): d020, P035, P038, A051, A052
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 0-10V input is used by P038
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A110
[Anlg 0-10V In Lo] or by
setting A051
- A052 [Digital Inx Sel] to option 26 “Anlg Invert”.
Values Default 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A112 [Anlg In4-20mA Lo] Related Parameter(s): d021, P034, P038, A051, A052
Sets the analog input level that corresponds to P034 [Minimum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than A113
[Anlg In4-20mA Hi] or by
setting A051
- A052 [Digital Inx Sel] to option 26 “Anlg Invert”.
Values Default 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A113 [Anlg In4-20mA Hi] Related Parameter(s): d021, P035, P038, A051, A052
Sets the analog input level that corresponds to P035 [Maximum Freq] if a 4-20mA input is used by
P038 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A112
[Anlg In4-20mA Lo] or
by setting A051
- A052 [Digital Inx Sel] to option 26 “Anlg Invert”.
Values Default 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%