PowerFlex 700 Adjustable Frequency AC Drive Quick Start 23
DYNAMIC CONTROL
Load Limits
151 [PWM Frequency]
Sets the carrier frequency for the PWM
output. Drive derating may occur at
higher carrier frequencies. For derating
information, refer to the PowerFlex
Reference Manual.
Default:
Min/Max:
Units:
4 kHz
2/10 kHz
1 kHz
Stop/Brake Modes
155
156
[Stop Mode A]
[Stop Mode B]
Active stop mode. [Stop Mode A] is
active unless [Stop Mode B] is selected
by inputs.
(1)
When using options 1 or 2, refer to the
Attention statements at [DC Brake Level]
in the User Manual.
Default:
Default:
Options:
1
0
0
1
2
3
“Ramp”
“Coast”
“Coast”
“Ramp”
(1)
“Ramp to Hold”
(1)
“DC Brake”
157
158
159
[Stop/Brk Mode A]
[Stop/Brk Mode B]
See description above.
Restart Modes
169 [Flying Start En]
Enables/disables the function which
reconnects to a spinning motor at actual
RPM when a start command is issued.
Not required in Flux Vector mode when
using an encoder.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
170
UTILITY
Drive Memory
196 [Param Access Lvl]
Selects the parameter display level.
Basic = Reduced param. set
Advanced = Full param. set
Default:
Options:
0
0
1
2
“Basic”
“Basic”
“Advanced”
“Reserved”
201 [Language]
Selects the display language when using
an LCD HIM. This parameter is not
functional with an LED HIM.
Default:
Options:
0
0
1
2
3
4
5
6
7
8-9
10
“Not Selected”
“Not Selected”
“English”
“Francais”
“Español”
“Italiano”
“Deutsch”
“Reserved”
“Português”
“Reserved”
“Nederlands”
Faults
240 [Fault Clear]
Resets a fault and clears the fault queue.
Default:
Options:
0
0
1
2
“Ready”
“Ready”
“Clear Faults”
“Clr Flt Que”
File