Loading...
Programming and Parameters 3-25
SPEED COMMAND
Speed Reference
096 [TB Man Ref Sel]
Sets the manual speed reference source
when a digital input is configured for
“Auto/Manual.
(1)
“Analog In 2” is not a valid selection if it
was selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep-Wake Ref]
Default:
Options:
1
1
2
3-8
9
“Analog In 1”
“Analog In 1”
“Analog In 2”
(1)
“Reserved”
“MOP Level”
097
098
097 [TB Man Ref Hi]
Scales the upper value of the [TB Man
Ref Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
[Maximum Speed]
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
096
098 [TB Man Ref Lo]
Scales the lower value of the [TB Man
Ref Sel] selection when the source is an
analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
096
099 [Pulse Input Ref]
Displays the pulse input value as seen at
terminals 5 and 6 of the Encoder
Terminal Block, if [Encoder Z Chan],
parameter 423 is set to “Pulse Input.
Default:
Min/Max:
Units:
Read Only
–/+420.0 Hz
–/+25200.0 RPM
0.1 Hz
0.1 RPM
Discrete Speeds
100 [Jog Speed]
Sets the output frequency when a jog
command is issued.
Default:
Min/Max:
Units:
10.0 Hz
–/+[Maximum Speed]
0.1 Hz
079
[Jog Speed 1]
Sets the output frequency when Jog
Speed 1 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
101
102
103
104
105
106
107
[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed
command value. In bipolar mode
direction is commanded by the sign of
the reference.
Default:
Min/Max:
Units:
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
60.0 Hz/1800 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
079
090
093
108 [Jog Speed 2]
Sets the output frequency when Jog
Speed 2 is selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
File
Group
No.
Parameter Name & Description
See page 3-2 for symbol descriptions
Values
Related
Vector
Vector
Vector
Standard
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector
Vector

Table of Contents