© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Installation
1300003 (EN)
16
Electrical Connection
For U.S. and Canada only – NOTE: Branch circuit
protection must be provided for the flatwork
finishers and be installed in accordance with the
National Electrical Code NFPA 70 (in Canada, in
accordance with CSA C22.1). Please refer to the
tables below for rating and supply requirements
(wire size).
For CE only – NOTE: Adequate circuit protection
must be provided for the flatwork finishers and be
installed in accordance with regional electrical
codes.
IMPORTANT: Electrical specifications in Ta bl es 1
and 2 are subject to change without notice. Always
refer to product serial plate for most current
specifications of product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit
breaker.
Electric Models
Serial Plate Rating Model Wire Size
Branch Circuit
Breaker
Full Load Amps
208/240/60/3
UD13F063 3 x 6 AWG
(3 x 16 mm
2
)
60 47
UD13F078 and
UD13F079
3 x 4 AWG
(3 x 25 mm
2
)
80 58
UD13F126 3 x 1/0 AWG
(3 x 70 mm
2
)
150 100
230/50/3
UD13F063 4 x 6 AWG
(4 x 16 mm
2
)
60 42
UD13F078 and
UD13F079
4 x 4 AWG
(4 x 25 mm
2
)
70 53
UD13F126 1 AWG (42.4 mm
2
) 125 93
400/50/3
UD13F063 5 x 8 AWG
(5 x 10 mm
2
)
35 26
UD13F078 and
UD13F079
5 x 8 AWG
(5 x 10 mm
2
)
45 33
UD13F126 4 AWG (21 mm
2
)70 53
Table 1
Gas Models
Serial Plate Rating Wire Size Branch Circuit Breaker Full Load Amps
120/60/1
3 x 14 AWG (3 x 2.5 mm
2
)15 7.5
230/50/3
3 x 14 AWG (3 x 2.5 mm
2
)15 4.8
400/50/3
5 x 14 AWG (5 x 2.5 mm
2
)15 4.7
Table 2