PARAMETER VALUES DEFAULT
SPh
0 = Check input PH1 when "CLOSED GATE".
1 = Ignore input PH1 when "CLOSED GATE".
1
Mode of intervention PH2 photocell input
The engagement of the connected photocell on the PH2 input always involves the temporary stop of the movement, until the photo-
cell is released. Once released, automation always moves in the direction of opening.
With this parameter you can customize when this behaviour is enabled.
Value 0: Enabled during opening and closing movement.
Value 1: Only enabled during the opening movement.
PARAMETER VALUES DEFAULT
Ph2
0 = Enabled in both opening and closing.
1 = Only enabled on opening.
0
Function of self-test of photocells
NOTE
• To properly use this function you need to use terminal number 23 to power the transmitter photocell.
By enabling this function it is possible to make the control unit perform a functional test of the photocells before each movement.
The test, if enabled, is not performed in case of fast reversals.
PARAMETER VALUES DEFAULT
tPh
OFF = Disabled.
1 = Enabled for input PH1
2 = Enabled for input PH2
3 = Enabled for both inputs PH1 and PH2
OFF
GND
25242318
1 2 3 4 5
RX
+ - COM NO NC
1 2
+ -
TX
+24VCOM PH1
10
+24V
TEST