4.3.3 Alarm and Control Output Relays
Each L-ADIO contains six Form C alarm output relays to extend alarms and control external apparatus.
Each internally generated alarm or control signal may be mapped to any of the six relays, disconnects
or other contractors, up to a 50Att maximum load.
4.3.4 LEDs
Each HV-ADIO contains two LEDs for Power and Comms status indication.
4.3.5 P-Out Connector
This port is used to power the CXC HP module. The maximum load is 0.7A or other low voltage ADIOs.
4.4 Redundant Input Power Module
The redundant input power module (RIPM) provides multiple power inputs to power the CXC HP
controller and any I/O peripherals such as the L-ADIO. The unit enables users to wire system power
into the control devices from multiple locations (e.g., on battery and load side of LVD’s) and provides
Diode-Or protection between power inputs.
Figure 11: Redundant Input Power Module
LED Color Status Indicator
Power Blue Power present to the device
Comms Green L-ADIO has been acquired by the
CXC HP