0180036-J0 Rev E Page 13
5 Specifications
5.1 Specifications: L-ADIO and 6I-ADIO
Table 2: Specifications: 3RU Rack Mount CXC HP (Sheet 1 of 4)
Cordex Controller Panel/Rack Mount
Basic Unit
Input Voltage: 12V to 60Vdc within rated limits
Electrical Ratings: Controller: 10 to 60Vdc, 1.6A max.
L-ADIO: 10 to 60Vdc, 1.6A max.
6I-ADIO: 10 to 60VDC, 0.2A max
MTBF: 472,000 @ 25°C (77°F)
EMC: The unit meets requirements of:
ICES-003 Class B
EN 55022 Class B (CISPR 22)
ETSI EN 300-386 Class B
EN 61000-4-2 ESD*
EN 61000-4-3 Radiated Immunity
EN 61000-4-4 EFT /Burst
EN 61000-4-6 Conducted Immunity
EN 61000-4-5 Surge
FCC Part 15 Class B
*NOTE: A grounded wrist strap is required when wiring to L-ADIO peripherals.