Manual operations
FK 3-1 / FK 3-06 motor-wound spring
operating mechanism
21.5.2003
© ALSTOM
48.020.181E/2
7/26
Operating mecha-
nism mounted on
circuit breaker and
coupled
The following manual operations can be performed for inspection pur-
poses and to remedy problems:
Manual discharge
of closing spring
Slow
opening
Slow
closing
Slow
opening
Slow
closing
If Action
Fig.
Closing spring discharged,
circuit breaker position indi-
cator OPEN
For inspection and ad-
justment
Slowly close
Fig.
Closing spring charged, circuit
breaker position indicator
OPEN
For inspection and ad-
justment
Circuit breaker must not
be closed
Slowly close
Manually discharge closing
spring
Fig.
Closing spring discharged,
circuit breaker position indi-
cator CLOSED
For inspection and ad-
justment
Slowly open
Fig.
Closing spring charged, circuit
breaker position indicator
CLOSED
For inspection and ad-
justment
Slowly open