Manual operations
FK 3-1 / FK 3-06 motor-wound spring
operating mechanism
21.5.2003
© ALSTOM
48.020.181E/2
22/26
The return stop will not function properly if the clamp shackle screw is
not tightened to the specified torque.
If the closing spring is being charged by the motor under these condi-
tions and the motor voltage drops out, the closing spring will discharge
by turning the gearing backwards. Damage to the operating mechanism
may result.
CAUTION
After performing manipulations on the return stop, tighten the
clamp shackle mounting screw to a torque of 5 Nm ±10%.
Re-enable motor limit
switch
Remove motor limit switch disabling plate 71.16 so that the motor limit
switch can function again.