EasyManua.ls Logo

Ametek NetWave 3.1 - Page 75

Ametek NetWave 3.1
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AMETEK CTs NetWave
The following steps are required to setup NetWave Cascade Source :
- The NetWave Master (L,+) is setup in the menu “Standalone/Master/Slave” to the mode “Master (L1, L,+). The
Source is set to function “CascadeSource”.
The NetWave works as a Master in parallel
mode and is phase L or +. The controller
controls the connected Slave NetWave.
- The NetWave Slave (N,-) is setup in the menu “Standalone/Master/Slave” to the mode “Slave (L2, N,
-)”.
The NetWave works as a Slave in parallel
mode and is phase N or -. The controller is
inactive. The NetWave hardware is
controlled by the NetWave Master.
- The Framebus OUT of the NetWave Master (L,+) is connected to the Framebus IN of the NetWave
Slave (N,-)
- The Framebus IN of the NetWave Slave (N,-) muss be terminated with
a Framebus Terminator.
- At the Signal OUT1 of the NetWave Master (L,+) a BNC T-Adapter
is connected.
- The Signal OUT1 (BNC T-Adapter) of the NetWave Master (L,+)
is connected to the Signal IN1of the NetWave Master (L,+)
- The Signal OUT1 (BNC T-Adapter) of the NetWave Master (L,+)
is connected to the Signal IN2 of the NetWave Slave (N,-).
- Each NetWave is supplied.
- Switch the PE at NetWave Master (L,+) to ground.
- Switch the PE at NetWave Slave (N, -) to floating.
- The PC computer is only connected to the NetWave Master (L,+).
- The EUT is connected to each NetWave.
The N from each NetWave are not connected.
The PE from each NetWave are not connected.

Table of Contents

Related product manuals