16
A01-00055 Rev N
Silence button or unplugging the UPM. When this nal test is completed,
the UPM will be ready to use.
Reference the below UPM fault code chart to identify the status of the UPM.
UPM Status Code Denition
IF Inverter fault
BE Back-Feed fault
HL Unit is off due to a high line
LL Unit is off due to a low line
DB Unit is off due to a low battery
FF Fan fault
SF Site wiring fault
NOTE:
If the UPM is on continuously, it will perform an auto battery test
every six days.
If you are utilizing MopUPS Pro software or the iSitePRO network
adapter, you can congure the system to automatically self-test
periodically.
The UPM is shipped with a charged battery, but some discharge
naturally occurs during storage and shipment. You may use the
UPM immediately, but you should realize that backup time may be
less than the stated rating until the UPM battery has had at least
six hours to charge.
AMETEK Powervar recommends that you do not plug laser
printers into the UPM. Laser printers are known to draw large
amounts of current when the fuser/heater assembly is energized.
Laser printers can easily overload the UPM or create a low voltage
condition that can interfere with the operation of the Voltage
Manager circuit.