26
A01-00055 Rev N
6.0 SPECIFICATIONS
North American Models ABCE422-11 and ABCE422-11MED
ABCE422-11
50042-02R
ABCE422-11MED
50042-22R
Type Standard Medical Grade
Power Rating (VA/Watts) 420 / 378 420 / 378
Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave
Transfer Time 4 ms. Typical 4 ms. Typical
Frequency 60 Hz. 60 Hz.
BTU/Hr. 140 140
T.H.D. w/100% Resistive Load <4% On Battery <4% On Battery
Online Efciency (w/o Charger) 90% 90%
Input Voltage 120 120
Input Current 5.18 Amps 5.18 Amps
Output Voltage 120 120
Output Current (VA/Watts) 3.50 / 3.20 Amps 3.50 / 3.20 Amps
Input Voltage Range
(w/o Using Battery)
96 to 144 Volts 96 to 144 Volts
Output Regulation (On Mains) ± 10% ± 10%
Output Regulation (On Battery) ± 5% ± 5%
Backup Time at Full Load (0.7 P.F.) 5 Minutes 5 Minutes
Floor Mountable Yes (Optional) Yes (Optional)
Communications Interface DB9, USB DB9, USB
Shipping Weight (lbs.) 37 37