Hardware Installation
B-2 CMX 240 Series Installation Guide
Set the tank probe switches as follows:
1. Set the second and third switches to ON for Andover Controls
software. If they are not ON (enabled), you do not see error
messages.
Figure B-1 shows the settings for switches 2 and 3 on the probe.
Figure B-1. Switch Settings for Switches 2 and 3 on Tank
Probe
Note
The Power Supply Override should be set to OFF because you do not
want to override the power supply.
2. Set the switch 1 to OFF to not override the power supply.
3. Set switches 4 through 9 to the address that corresponds to the
channel number of the probe.
Figure B-2 shows the address switch settings for the tank probe
channels 1 through 6. Be sure that the probe you assign to channel 1
in the
Point
window is set to address 0, as shown. The other
channels correspond to subsequent address numbers.
Refer to the MTS Systems Corporation documentation for further
information on how to set the address switches.
123456789ON
Data Error Detection Enabled
Communication Time-out Timer Enabled
Set Other Switches for Address of Probe
Power Supply Override