Rev. A2, 07/16 PG7
15
Automation Products Group, Inc.
Bar Graph 0% (bAR 0) & Bar Graph 100% (bAR100)
Settings:
Allows the user to dene the reading values associated with 0%
and 100% on the display bar graph. Bars will appear/disappear in
10% increments of the total span between the two values.
NOTE: The 0% reference does not have to be the lower pressure setting; 0%
can be set as the higher pressure setting, thereby causing the bar graph to
increase as the pressure decreases. Negative pressure settings can also be
used as either the 0% or 100% reference points.
Setting the Display Bar Graph:
Step 1: Press the On/O button once to enter the main setup menu.
Step 2: Press (Z) to cycle through the options until AdVSET is displayed.
Step 3: Press (S) to access the Advanced Settings menu.
Step 4: Press (Z) to cycle through the options until BAR 0 is displayed.
Step 5: Press (S) to access the Bar Graph 0% value. A 5-digit number will
appear with the rst digit ashing.
Step 6: Press (Z) to change the value of the rst ashing digit (options: 0-9
or “-”).
Step 7: Press (S) to accept the value of the ashing digit and advance to the
next digit. Repeat steps 6 and 7 until the desired 0% reading is fully
entered. After the last digit is accepted by pressing (S), the display will
return to the advanced setup menu.
Step 8: Press (Z) to cycle through the options until BAR100 is displayed.
Step 9: Repeat Steps 5-7 to enter the Bar Graph 100% value.
Step 10: To exit the advanced setup menu, press (Z) until EXIT is displayed
and press (S) to exit to the main setup menu.