EasyManua.ls Logo

APG PG-7 - Maximum;Minimum Reset

APG PG-7
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PG7 Rev. A2, 07/16
8
Automation Products Group, Inc.
Maximum/Minimum Reset (MAXMIN):
Pressing the (S) button while in standard operating mode will cycle between
displaying the current pressure reading, the Maximum pressure reading
and the Minimum pressure reading. The maximum and minimum readings
will be stored until the gauge is powered down or the max/min readings are
reset.
Resetting the Max/Min readings:
Step 1: Press the On/O button once to enter the main setup menu.
Step 2: Press (Z) to cycle through the options until MAXMIN is displayed.
Step 3: Press (S) to access the Max/Min reset options.
Step 4: Press (Z) to toggle between YES and NO until YES is displayed.
Step 5: Press (S) to reset the Max/Min readings and return to the main
setup menu.
www. .com
information@itm.com1.800.561.8187

Related product manuals