Rev. B2, 8/16 PG10
15
Automation Products Group, Inc.
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • sales@apgsensors.com
Bar Graph 0% (bAR 0) & Bar Graph 100% (bAR100) Settings:
Allows the user to dene the reading values associated with 0% and 100% on
the 270
0
display bar graph. Bars will appear/disappear in 10% increments of the
total span between the two values.
NOTE: The 0% reference does not have to be the lower pressure setting;
0% can be set as the higher pressure setting, thereby causing the bar graph to
increase as the pressure decreases. Negative pressure settings can also be used
as either the 0% or 100% reference points.
Setting the Display Bar Graph:
Step 1: Press once to enter the main setup menu.
Step 2: Press or to cycle through the options until AdVSET is
displayed.
Step 3: Press to access the Advanced Settings menu.
Step 4: Press or to cycle through the options until BAR 0 is displayed.
Step 5: Press to access the Bar Graph 0% value. A 5-digit number will
appear with the rst digit ashing.
Step 6: Press or to change the value of the rst ashing digit.
Step 7: Press to accept the value of the ashing digit and advance to the
next digit......repeat steps 6 and 7 until the desired 0% reading is fully
entered.
Step 8: Press or to cycle through the options until BAR100 is displayed.
Step 9: Repeat Steps 5-7 to enter the Bar Graph 100% value.
Step 10: To exit the advanced setup menu, press or until EXIT is
displayed and press to exit to the main setup menu.