E6 24 DTR.APC.APR.ALW.03(ENG)
3. Set alarm current mode to “High” (>21.5 mA) or “Low” (<3.7 mA), depending on PLC configuration, in
the “Specific parameters” tab.
Note:
During configuration of PLC response to alarm signal from the transmitter, take into account that
regardless of “High” or “Low” setting some critical alarms from the transmitter can be signalled
always by “Low” alarm, irrespective of the above settings.
4. User may select refreshing time of the converter -ADC in the “Filtration” tab. Do not set time to 32 ms
for operation in functional safety loop because in this operation mode the converter will not proceed
verification of the current output.
NOTE:
The transmitter should be protected against modification of its settings after making the above described
and the other necessary changes. For this purpose:
5. Set “Local operation” to “Disabled” in the “LCD” tab to prevent change in parameters using local
MENU buttons.