E6 33 DTR.APC.APR.ALW.03(ENG)
5.4. APR2000GALW, Measurement ranges and metrological parameters
5.4.1 APR2000GALW. Measurement ranges
N
Nominal range (FSO)
Minimum set range
Overpressure limit
Static pressure limit
1
0...25mbar (0...2500Pa)
1mbar (100Pa)
1bar
350mbar
2
-2.5...2.5mbar (-250...250Pa)
0.2mbar (20Pa)
350mbar
350mbar
3
-7...7mbar (-700...700Pa)
1mbar (100Pa)
350mbar
350mbar
4
-25...25mbar (-2500...2500Pa)
5mbar (500Pa)
1bar
1bar
5
-100...100mbar (-10...10Pa)
20mbar (2kPa)
1bar
1bar
5.4.2. APR-2000GALW Permitted environmental conditions
Operating temperature range -30º ÷ 85ºC
Operating temperature range for intrinsic-safe versions in accordance with Appendix Exi.ATEX
or Appendix Exi.IECEx.
Thermal compensation range -10º ÷ 70ºC
Relative humidity max 98% with condensation
5.4.3. APR2000GALW. Metrological parameters.
Nominal range
0...25mbar
-2.5...2.5mbar
-7...7mbar
-25...25mbar
-100...100mbar
Accuracy
0.075 %
0.25 %
0.1 %
0.1 %
0.075 %
Thermal error
0.1 % (FSO)/ 10ºC, max 0.4 % (FSO) for the whole thermal compensation range
Additional electronic damping
0...30 s
5.4.4. APR2000GALW. Construction materials
M20x1.5/6x1 adapter brass
Valve manifold 1.4404 (316L)
Valve manifold adapter 1.4404 (316L)
1/4 NPT connector brass, 1.4404 (316L) or galvanized St3S carbon steel
(Other materials as given in 5.1.2 for APR...)
5.4.5. APR2000GALW. Pressure Connectors
- The terminals fit adapted to Ø6x1 plastic tubes,
- Valve manifold adapter or 1/4 NPT connector (see p. 8.3 and Fig.18).
5.5. APR2000YALW. Measurement ranges and metrological parameters
5.5.1. APR2000YALW. Measurement ranges.
5.5.2. APR2000YALW Permitted environmental conditions
Operating conditions as in section 5.3.3 for APR…
5.5.3. APR2000YALW. Metrological parameters.
* zeroing in static pressure conditions with zero differential pressure eliminates this error;
Medium density range up to 1.1 g/cm
3
(standard version)
over 1.1 g/cm
3
(special version by arrangement with Aplisens)
N
1
2
Nominal range
0... 6000 mmH
2
O
0... 1600 mmH
2
O
Minimum set range
600 mmH
2
O
160 mmH
2
O
Static pressure limit
40 bar
Nominal range N
1
2
Accuracy for nominal range
± 0.16 %
± 0.2 %
Accuracy for minimum range
± 0.5 %
± 0.6 %
temperature error
0.4 % for temperatures 25º...+80ºC
Zero shift error from static pressure *
0.08 % / 10bar
0.1 % / 10bar