E6 44 DTR.APC.APR.ALW.03(ENG)
The selected unit should be confirmed by pressing [◙].
After approval the parameter transmitter will confirm the party of command by the "DONE" or report the error
number. The "← BACK" cause goes up one level.
Descriptions:
Local Menu
Submenu
Notice
EXIT
Return from the local Menu to the normal operation of the transmitter
PVZERO
Pressure zeroing
SETLRV
Setting the lower range of values set by the done pressure
(no change of span)
BYPRES
Set across set pressure
BYVALU
Set across inscribing of value (after approval at display the current
value will appear before the passage in edit mode)
+/-______
Select and confirm sign introduced parameter. Introduce in sequence,
digit after digit, 5 digital numbers with point or without point. After
confirmation the last 5 digit of the parameter transmitter will confirm
the party of command by the "DONE" announcement or the proper
number of error will notify. The parameter will be written down in units
"UNIT".
SETURV
Set the upper range value by the done pressure
UNIT
Menu process variable units
IN_H2O
inches of water at a temperature of 68° Fahrenheit
IN_HG
inches of mercury at a temperature of 68° Fahrenheit
FT_H2O
Foot of water a temperature of 68° Fahrenheit
MM_H2O
mm of water at a temperature of 68° Fahrenheit
MM_HG
mm of mercury at 0°C
MBAR
millibar
G/SQCM
grams per square centimetres
KG/SQCM
kilogram per square centimetres, technical atmosphere
KPA
kilopascal
TORR
tor (mm Hg)
ATM
physical atmosphere
M_H2O
meter of water at 4ºC
MPA
Megapascal
INH2O4
inch of water at a temperature of 4ºC
MMH2O4
mm of water at 4ºC
DAMPIN
set of the solid temporary suppression of the process variable
TRANSF
set of the current output form
LINEAR
linear
SQRT
square root
SPECIA
user’s special
SQUARE
square
%SQRT
Square root characteristic cut-of point setting
LCD1VR
Assigning a process variable to LCD1
CURREN
On LCD1 will displayed current value in current loop in [mA]
PERCEN
The percent value output signal will displayed on LCD1- controlling
in%
LCD2VR
Assigning a process variable to LCD2
PRESS
The pressure value will displayed on LCD2
USER
The user’s units will be displayed on LCD2. Scaling of the user range
and record of the user units can be made using a computer or
communicator, see → HART command No. 244.245.
SENS_T
The current temperature of pressure sensor will displayed on LCD2
CPU_T
The current temperature of the transmitter CPU will displayed on
LCD2 - in ºC