Page 20
RELAY FUNCTIONS
1 324 756 8
4. Dip-Switch Settings
a. Interlocked Functions
Interlocked means the two adjacent push buttons can not be activated simultaneously at the
same time as it will cancel each other out. Interlocked settings are usually applied to crane’s
forward and reverse motions. Each dip-switch on the decoder module corresponds to one (1)
motion or two (2) adjacent push buttons (refer to Fig. 14 & 15 below). Only the first 7
dip-switch positions are used (counting from left to right), the 8
th
dip-switch position (far right)
is not used.
(Fig. 14)
(Fig. 15)
Manufacture preset
Dip Settings Function Descriptions
# of Relays
Used
0000000 Normal Interlocked
2
0000110 On (right button) & Off (left button)
2
0001000
On & Off affected by the e-stop command. When E-stop
command is initiated, the Off relay is activated.
2
0001001
On + Start / Off + Start -- Prior to pressing the button you must
first rotate and hold the power key switch at START
position to activate On or Off relays.
2
0000111 Safety Magnet On & Off
2
0001010 FWD/REV toggled (latching)
2
0010000 Normal Interlocked + External Warning*
2
* External warning function requires installing an external warning device such as horn and rotating lights to the function
relay output.