Figure 5 Required bridging when the car top and pit
inspection connected
The bridging should be only done during the first
installation. After the car top and pit inspection
terminals are connected, the bridges must be
removed!
4.2 Auto Tuning Parameter Settings
Take the lift to recall mode by switching the recall key
(SEE) to “1” position in the recall terminal located in the
control panel. In this step, the motor can be moved by up
and down buttons (SEEU, SEED).
Figure 6 Recall terminal
After making the system prepared to auto tuning, the
required parametric settings must be done on LCD
screen.
Turn on all the fuses on ARCUBE, then turn on “SMP”
switch over the distribution panel.
After the screen is displayed, press “ENT” button in
order to enter the menu. When you see “QUICK
INSTALLATION” screen, press “ENT” button one
more time and set the parameters as shown below step by
step according to your system.
4.2.1 Operation mode
This should be chosen correctly depending on if the car
top and pit inspection terminal is connected or not.
4.2.2 Motor type
Motor type must be chosen correctly as asynchronous or
synchronous.
4.2.3 Motor control type
Motor control type must be chosen correctly as open
loop or closed loop.
*Only closed loop option exists for the synchronous
motors.