Temperature Output Calculation ° Celsius
Temperature Output Calculation ° Fahrenheit
Position Output Calculation % of max open position
Position Output Calculation 1/4 Turn application in Degrees
Position Output Calculation Emech F3 application in Degrees
Temperature Output (°C) = (7.143 x Current Output (mA)) - 35.714
Temperature Output (°F) = (12.857 x Current Output (mA)) - 32.286
Position Output (%) = (7.143 x Current Output (mA)) - 35.714
Position Output (Deg.) = (6.429 x Current Output (mA)) - 32.143
Position Output (Deg.) = (16.429 x Current Output (mA)) - 82.142