Ascon Tecnologic - K31D - OPERATING INSTRUCTIONS - PAG. 14
7. PROGRAMMABLE PARAMETERS
Hereafter is inserted a description of all the parameters available on the instrument. Some of them may not be present,
either due to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.
Group ]sp Set Point Parameters
Parameter Description Range Default Note
1
nSP
Number of the programmable Set Points 1 ÷ 2 1
2
SPAt
Active Set Point 1 ÷ nSP 1
3
SP1
Set Point 1 SPLL ÷ SPHL 0
4
SP2
Set Point 2 SPLL ÷ SPHL 0
5
P2HL
Upper Pr2 measurement limit for differential control -1999 ÷ 9999 9999
6
P2LL
Lower Pr2 measurement limit for differential control -1999 ÷ 9999 -1999
7
SPLL
Low Set Point -1999 ÷ SPHL -1999
8
SPHL
High Set Point SPLL ÷ 9999 9999
Group ]InP Measure Input Parameters
Parameter Description Range Default Note
9
SEnS
Probes type
Ptc PTC
ntc NTC
Pt10 Pt1000
ntc
10
Pr2
Probe Pr2 presence
yES
no
yES
11
dP
Number of decimal figures 0/1 0
12
Aot
Analogue control Output type
0-20 0 ÷ 20mA
4-20 4 ÷ 20 mA
0-10 0 ÷ 10 V
2-10 0 ÷ 10 V
0-10
13
Unit
Temperature unit of measurement °C/°F °C
14
FiL
Input digital filter
oFF Not active
0.1 ÷ 20.0 s
1.0
15
oFS1
Measuring Offset Pr1 -1999 ÷ 9999 0
16
oFS2
Measuring Offset Pr2 -1999 ÷ 9999 0
17
rot
Rotation of the measuruing straigìht line 0.000 ÷ 2.000 1.000
18
InE
oPE functioning in case of measuring error
or Overrange
Ur Under range
our Overrange and underrange
our
19
oPE
Output power in case of measuring error -100 ÷ 100% 0
20
dIF
Digital inputs function
noF No Function
Aac Reset Alarms latch
ASi Acknowledged Alarms
HoLd Hold Measure
oFF Control OFF
CHSP Sequential Set Point selection
SP1.2 SP1 or SP2 Set Point selection
HE.Co Select HEAt with SP1 or CooL with SP2
noF
Group ]Out Outputs Parameters
Parameter Description Range Default Note
21
O1F
Output 1 function
1.rEG Control output 1
2.rEG Control output 2
ALno Alarm Output NO
ALnc Alarm Output NC
ALni Alarm Output NC with reversed LED functioning
1.rEG
22
O2F
Output 2 function ALno
23
O3F
Output 3 function ALno
24
O4F
Output 4 function ALno