EasyManuals Logo

ascon M3 Series User Manual

ascon M3 Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
By a sole PID control algorithm, the
controller handles two different out-
puts, one of these performs the
Heat action, the other one the Cool
action.
It is possible to overlap the out-
puts.
The dead band parameter
#d.bnd,
is the zone where it is possible to
separate or overlap the Heat and
Cool actions.
The Cool action can be adjusted
using the relative cool gain para-
meter #r.C.Ga.
To limit the Heat and Cool outputs
the parameters
#0p. H and #0p.HC
can be used.
When there is an overlap, the dis-
played output
# OUt shows the
algebric sum of the Heat and Cool
outputs.
32
4 - Operations
SECOND GROUP HEAT COOL CONTROL
Soft-start
control output
value
Value of the control output during
the Soft-start activation time.
Soft-start
activation time
Time duration (starting from the
power on) of the Soft-start func-
tion.
Output
Safety Value
Output Value in case of input
anomaly
#SA.OP
Soft-start
100%
Power on
#St.tM
#St.OP
OP
Time
#st.tM
#st.Op
Controller
address
the address range is from 1 to 247
and must be unique for each con-
troller on the communication bus
to the supervisor.
When set to
Off the controller is
not communicating
#Addr

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ascon M3 Series and is the answer not in the manual?

ascon M3 Series Specifications

General IconGeneral
Brandascon
ModelM3 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals